Laboratory airflow control speciality design requirements / 實(shí)驗(yàn)室氣流控制系統(tǒng)設(shè)計(jì)要求
In any case, air should always flow from the office, the corridor and auxiliary areas into the lab area. And all chemical laboratory exhaust gas should be directly discharged to the outside, and mustn’t be recycled. Therefore, unless chemical laboratory is required to clean itself, its relative to other space within a building maintains negative pressure of the camp.
Experiment indoor airflow should be from low risk areas to high risk areas. Generally speaking, it should keep the flow of gas 47 liters per second between the above area (170 cubic meters per hour). Office areas in a laboratory should always maintain a positive pressure relative to the corridor and laboratory.
Under normal conditions, 6-12 times every hour’s room air changes are considered appropriate. When there is analysis equipment which is likely to produce high heat load or there is large local exhaust air in the room, there will be a need to increase in volume.
In order to ensure the safety of the staff, keep the distance of discharge point and flat roof at least 3 meters (ten feet) or even higher in order to exhaust emissions and effectively diluted. The specific choice should be calculated to confirm.
Interpretation of variable air volume speciality / 解讀變風(fēng)量系統(tǒng)
In the large ventilation system, in order to solve the ventilation equipment at the end of the variable air volume demands and constant wind speed and to achieve further adjustment, we apply the frequency conversion and variable air volume ventilation control.
Interpretation of the variable air volume speciality
解讀變風(fēng)量系統(tǒng)
Laboratory airflow control aims
實(shí)驗(yàn)室氣流控制目標(biāo)
Security (Accord with the regulations and standards)
安全性(符合規(guī)范要求)
Local exhaust control
局部排風(fēng)控制
Regional pressure control
區(qū)域壓力控制
Energy-saving
降低能耗
Easy to maintenance and management
易維護(hù)管理
Availability and flexibility
系統(tǒng)靈活性
Adaptive control (Temperature and humidity)
舒適性控制(溫濕度)
Variable air volume control ventilation:Every country has strict requirements of the ventilation cabinet winds, For laboratory ventilation cabinet is the most important level of protective equipment. Generally we should always maintain constant ventilation counter wind speed of 0.5 m/s. Too high or too low surface wind speed can produce dangerous side leakage.
Local exhaust control: Cover cabinet , atomic absorption, reagent cabinets and some other local exhaust control should be able to continuously and effectively control and discharge the exhaust gases quickly and securely.
Room pressure control: Generally we should maintain negative pressure of the laboratory relative to that of the corridor in order to avoid cross contamination of the office or production areas.
The working principle of ventilation counter wind speed control system / 通風(fēng)柜面風(fēng)速控制系統(tǒng)工作原理
1、Surface wind speed control system continuously monitor s the actual exhaust air volume of the fume cabinet . Calculate the average wind speed of the open area according to the height of the window. When the exhaust pipe pressure changes or the window height changes, the system responses within a second and adjust the opening of the air valve to keep the average surface wind speed of the window open surface stable.
2、Under different experimental conditions, we can set different parameters on the panel.
不同實(shí)驗(yàn)狀況時(shí),可在面板上設(shè)置不同的參數(shù)。
3、The system controls surface wind speed at a set speed ( 0.5m/s) through infrared detector when there is an operator in front of the ventilation cabinet and the system automatically switches to another value(e.g. 0.3m/s) to save costs when there is no operator in front of the fume cabinet .
4、When ventilation cupboard door was off, the air valve maintains the minimum of the ventilation cabinet exhaust air 1500MM , the ventilation cabinet 300CMH.
5、Due to the fault surface wind speed is high or low, there will be sound-light alarms.
由于故障面風(fēng)速過高或過低時(shí)有聲光報(bào)警。
6、When temperatures of ventilation cabinet are high, there will be sound-light alarms.
通風(fēng)柜溫度過高時(shí)有聲光報(bào)警。
7、When the position of the ventilation cabinet is too high, there will be sound-light alarms.
通風(fēng)柜門位過高時(shí)有聲音報(bào)警。
8、When there is an exception, open the emergency discharge mode control and the system will open all the air valves. The maximum air volume of the ventilation cabinet s is free from the control of the wind speed value.
We provide laboratory for variable air volume systems CON-LABC with VAV fume hood control system CON-FHC,using the world’s most advanced VAV solutions through a digital controller for laboratory supply and exhaust,fume hood face velocity for strict monitoring and control.
Security no matter how to adjust the opening window, you can always precise control of the fume hood wind speed of 0.5m/s+ 20% of imports. At the same time the exhaust valve air flow tracking changes in the amount of wind to send the air valve to increase or decrease exhaust volume to ensure that the design of the infiltration air flow is constant, thus ensuring a laboratory micro-negative pressure and airflow direction. System strong adaptability, and energy consumption can be decline to fully protect the safety on this premise.
We provide laboratory for variable air volume systems CON-LABC with VAV fume hood control system CON-FHC,using the world’s most advanced VAV solutions through a digital controller for laboratory supply and exhaust,fume hood face velocity for strict monitoring and control.
Security no matter how to adjust the opening window, you can always precise control of the fume hood wind speed of 0.5m/s+ 20% of imports. At the same time the exhaust valve air flow tracking changes in the amount of wind to send the air valve to increase or decrease exhaust volume to ensure that the design of the infiltration air flow is constant, thus ensuring a laboratory micro-negative pressure and airflow direction. System strong adaptability, and energy consumption can be decline to fully protect the safety on this premise.